ESS Protocol (BMS block)

Source document: Growatt xxSxxP ESS Protocol, rev 2.3, 2017-11-28 (Protocols/1xSxxP_ESS_Protocol_rev2.3_20171128.pdf)

Why this page exists

Protocol V1.39 documents the BMS block at input registers 1082-1124 by name only. Against the first row, register 1082 BMS_StatusOld, it carries this note and nothing else:

Detail information, refer to document: GrowattxxSxxP ESS Protocol

So V1.39 gives you the register names for the whole block and defers the units, scales and encodings to a separate document. That document is the one above, and it is the reason several of these registers were mapped by guesswork for a long time.

This is not a register map you can poll

The ESS Protocol describes the link between the inverter, the battery and an application program — a separate Modbus conversation in its own address space (0x0010-0x0052). You cannot read these addresses from the inverter.

What it gives us is the meaning of the values the inverter republishes in its own input registers at 1082+. The address correspondence below is the useful part.

Address correspondence

Evident from the names, and confirmed on hardware where marked.

ESS address ESS name V1.39 input register Unit / encoding
0x0010 Gauge IC current 1100 BMS_GaugeICCurr 10 mA
0x0013 Status 1083 BMS_Status bitfield
0x0014 Error 1085 BMS_Error bitfield
0x0015 SOC 1086 BMS_SOC % ✅
0x0016 Voltage 1087 BMS_BatteryVolt 10 mV ✅
0x0017 Current 1088 BMS_BatteryCurr 10 mA, two's complement ✅
0x0018 Temperature 1089 BMS_BatteryTemp °C, -127 to 127 ✅
0x0019 Max charge/discharge current 1090 BMS_MaxCurr —
0x001A Gauge RM 1091 BMS_GaugeRM 10 mAh
0x001B Gauge FCC 1092 BMS_GaugeFCC 10 mAh
0x001C YW / FW 1093 BMS_FW byte 1 hardware, byte 2 software
0x001D Delta 1094 BMS_DeltaVolt V, cell voltage
0x001E Cycle Count 1095 BMS_CycleCnt —
0x0020 SOH 1096 BMS_SOH bits 0-6 counter, bit 7 flag
0x0021 CV Voltage 1097 BMS_ConstantVolt 10 mV
0x0022 Warning 1099 BMS_WarnInfo bitfield

✅ = confirmed against instruments on an SPH3620 (#397): SOC against the inverter's own sensor, voltage against a meter reading 54.2 V, current against a clamp DC ammeter reading 16.4 A, temperature against a thermal camera.

The correspondence is not a fixed offset — 1082 BMS_StatusOld and 1084 BMS_ErrorOld are inverter-side copies with no ESS equivalent, which shifts the run.

The three that matter most

Current is 10 mA, not 100 mA

0x0017 is documented in units of 10 mA, so the scale is 0.01 A. Raw 1640 is 16.4 A.

This settled a real disagreement. Four SPH maps use 0.01, confirmed against a clamp meter; SPH_8000_10000_HU used 0.1, which was neither documented nor measured and was most likely taken by analogy from register 3170 Ibat, which genuinely is 0.1 A on the MIN/MOD range. Corrected to 0.01.

Current is signed, and the encoding is explicit

The document's "See Current explain" table:

Range Meaning
0x0000-0x7FFF current is positive
0x8000-0xFFFF current is negative

Plain two's complement. That is why these registers carry 'signed': True.

What it does not define

The spec fixes the numeric encoding and never states which physical direction is positive. Whether charging reads positive is a property of the firmware, not of this document.

On an SPH3620 it is the standard one — positive charging, negative discharging — confirmed in both directions against the reported power (#397):

State Current Voltage Implied Reported
Charging +44.30 A 54 V 2392 W ~2.4 kW
Discharging -54.00 A 53 V 2862 W 2.8 kW
Discharging -4.20 A 53 V 223 W 220 W

Those also confirm the 0.01 scale across a 13x range of magnitudes, from 4.2 A to 54 A.

Still one model, though. See Invert Battery Power if your battery power reads backwards — noting that option affects battery power and not battery current.

Temperature is whole degrees

0x0018 is documented as °C with a range of -127 to 127 — whole degrees, signed. Not tenths.

This matters because V1.39 documents the inverter's own battery temperature at register 1040 as 0.1C, and at least one SPH3620 populates 1040 from the BMS value without rescaling it — so 25 °C arrives as raw 25 and the documented scale renders it as 2.5 °C. The integration detects and corrects that at read time rather than changing the scale, because spec-compliant inverters do report tenths there.

Bitfields

The document also defines the status, error and warning bitfields behind registers 1083, 1085 and 1099. The integration does not currently decode them; the tables are in the PDF if anyone wants to.

Register ESS Contents
1083 BMS_Status 0x0013 bits 0-1 state (soft start / standby / charging / discharging), bit 3 cell balance, bit 4 sleep, bits 5-6 discharge and charge output, bit 7 terminal status, bits 8-9 master box mode, bits 10-11 SP status
1085 BMS_Error 0x0014 15 protection flags — over/under voltage, over-current charge and discharge, short circuit, over/under temperature for charge and discharge separately, MOS and environment temperature
1099 BMS_WarnInfo 0x0022 warning-level equivalents of the above, plus bits 14-15 giving battery chemistry (00 LiFePO4, 01 ternary lithium, 10 lithium titanate)

Applicability

The document is titled for the 1xSxxP family (SPF 5 kW, MHP 5 kW), and V1.39 references it generically as "GrowattxxSxxP" for the BMS block. Treat the units as reliable for the BMS block on SPH; treat anything model-specific with the usual caution, and prefer a measurement where one exists.